4.3.4 Accessing and Editing Parameters

Parameters in the drive and adapter can be edited with RSNetWorx
using the procedure in table 4.5. The adapter parameters are
appended to the list of drive parameters. In figure 4.5, for example,
the drive has 387 parameters, so parameter 388 is the first adapter
parameter.

Figure 4.4 – EDS Wizard Screen

Table 4.5 – Procedure to Access and Edit Parameters Using RSNetWorx

Step

Action

Icon

1.

After creating an EDS file, right-click on the
icon for the SP600 drive and adapter and
select Properties. The SP600 Drive dialog box
appears.

2.

Click the Device Parameters tab (figure 4.5).
If an EDS Editor message appears, click
Upload to load the parameter values in the
drive to the computer.

Parameters are displayed in numerical order
under Parameter. You can either scroll through
the list or select a specific group of parameters
in the Groups box. The available groups and
the numbers of the adapter parameters will
vary based on the type of drive that is
connected to the adapter.

3.

In the Current Value column, double-click a
value to edit it.

4.

Click Apply to save changes to the device.