Rockwell Automation RECOMM-DNET DeviceNet Adapter for use with DPI AC Drives User Manual
Page 35

Configuring the DeviceNet Adapter
4-11
Step 3. If desired, select an additional source of the data to output
to the network in Peer B Output (40). See figure 4.13.
Step 4. Set Peer Out Time (42) and Peer Out Skip (43) to establish
the minimum and maximum intervals between Peer
messages. The minimum interval is set in Peer Out Time
(42). The maximum interval is the value of Peer Out Time
(42) multiplied by the value of Peer Out Skip (43). See
figure 4.14.
Step 5. Set Peer Out Enable (41) to On. The adapter will transmit
the data selected in Peer A Output (39) and Peer B Output
(40) to the network. Another adapter must be configured to
receive the data.
Figure 4.12 – Peer A Output Screen on an LCD OIM
Figure 4.13 – Peer B Output Screen on an LCD OIM
Figure 4.14 – Min Peer TX Time and Peer Out Skip Screens on an LCD OIM
Port 5 Device
RECOMM-DNET
Parameter #: 39
Peer A Output
1
Cmd/Ref
Value
Description
0
Off (Default)
1
Logic Command/Reference
2-5
Datalink A, B, C, or D
Input
6-9
Datalink A, B, C, or D
Output
Port 5 Device
RECOMM-DNET
Parameter #: 40
Peer B Output
2
DL A Input
Value
Description
0
Off (Default)
1
Logic Command/Reference
2-5
Datalink A, B, C, or D
Input
6-9
Datalink A, B, C, or D
Output
Port 5 Device
RECOMM-DNET
Parameter #: 42
Peer Out Time
10.00
Secs.
0 <> 10.00
Port 5 Device
RECOMM-DNET
Parameter #: 43
Peer Out Skip
1
1 <>16