Configuring the DeviceNet Adapter

4-11

Step 3. If desired, select an additional source of the data to output

to the network in Peer B Output (40). See figure 4.13.

Step 4. Set Peer Out Time (42) and Peer Out Skip (43) to establish

the minimum and maximum intervals between Peer
messages. The minimum interval is set in Peer Out Time
(42). The maximum interval is the value of Peer Out Time
(42) multiplied by the value of Peer Out Skip (43). See
figure 4.14.

Step 5. Set Peer Out Enable (41) to On. The adapter will transmit

the data selected in Peer A Output (39) and Peer B Output
(40) to the network. Another adapter must be configured to
receive the data.

Figure 4.12 – Peer A Output Screen on an LCD OIM

Figure 4.13 – Peer B Output Screen on an LCD OIM

Figure 4.14 – Min Peer TX Time and Peer Out Skip Screens on an LCD OIM

Port 5 Device

RECOMM-DNET

Parameter #: 39

Peer A Output

1

Cmd/Ref

Value

Description

0

Off (Default)

1

Logic Command/Reference

2-5

Datalink A, B, C, or D

Input

6-9

Datalink A, B, C, or D

Output

Port 5 Device

RECOMM-DNET

Parameter #: 40

Peer B Output

2

DL A Input

Value

Description

0

Off (Default)

1

Logic Command/Reference

2-5

Datalink A, B, C, or D

Input

6-9

Datalink A, B, C, or D

Output

Port 5 Device

RECOMM-DNET

Parameter #: 42

Peer Out Time

10.00

Secs.

0 <> 10.00

Port 5 Device

RECOMM-DNET

Parameter #: 43
Peer Out Skip

1

1 <>16