Rockwell Automation RECOMM-DNET DeviceNet Adapter for use with DPI AC Drives User Manual
Page 57

Using I/O Messaging
6-3
An image that uses 32-bit words for Reference and Datalinks would
change the I/O image in figure 6.1 as follows:
Figure 6.2 illustrates an example of an I/O image that does not use
all of the I/O data. Only the Logic Command/Reference and
Datalink B are enabled. In this example, the Reference is a 32-bit
word, and Datalinks are 16-bit words.
Word
I/O
Word
I/O
0
Logic
Command/Status
7 - 10
Datalink B
1 - 2
Reference/Feedback
11 -
14
Datalink C
3 - 6
Datalink A
15 -
18
Datalink D
Figure 6.2 – Sample I/O Image with Only Logic/Reference and Datalink B
Enabled
Controller
Scanner
Module
SP600 Drive
DeviceNet
DPI
Output
Image
(Write)
Input
Image
(Read)
Message
Handler
Message
Buffer
Message
Handler
0 Logic Status
1 Feedback (LSW)
2 Feedback (MSW)
3 Datalink Out B1
4 Datalink Out B2
0 Logic Command
1 Reference (LSW)
2 Reference (MSW)
3 Datalink In B1
4 Datalink In B2
Logic Command
Reference
Data In A1
Data In A2
Data In B1
Data In B2
Data In C1
Data In C2
Data In D1
Data In D2
Logic Status
Feedback
Data Out A1
Data Out A2
Data Out B1
Data Out B2
Data Out C1
Data Out C2
Data Out D1
Data Out D2
Word and I/O
LSW = Least Significant Word (Bits 15 0)
MSW = Most Significant Word (Bits 31 16)