3 net a status indicator – Rockwell Automation RECOMM-DNET DeviceNet Adapter for use with DPI AC Drives User Manual
Page 84

8-4
DeviceNet Adapter for use with DPI AC Drives
8.1.3 NET A Status Indicator
Table 8.3 – NET A Status Indicator: State Definitions
State
Cause
Corrective Actions
Off
The adapter and/or
network is not powered
or adapter is not
connected properly to
the network.
• Securely connect the adapter
to the drive using the Internal
Interface cable and to the
network using a DeviceNet
cable.
• Correctly connect the
DeviceNet cable to the
DeviceNet plug.
• Apply power to the drive and
network.
Flashing
Red/
Green
The adapter has
received an Identify
Comm Fault request.
• Wait for the faulted node
recovery to complete.
Flashing
Red
A DeviceNet I/O
connection has timed
out.
• Place the scanner in RUN
mode, or apply power to the
peer device that will send I/O.
• Check the amount of traffic on
the network.
Solid
Red
Failed duplicate node
detection test or bus
off.
• Configure the adapter to use
a unique node address on the
DeviceNet network.
• Configure the adapter to use
the correct network data rate.
• Ensure network has correct
media installed.
Flashing
Green
The adapter is properly
connected but is not
communicating with
any devices on the
network.
• Place the controller in RUN
mode, or apply power to the
peer device that will send I/O.
• Program a controller or peer
device to recognize and
transmit I/O to the adapter.
• Configure the adapter for the
program in the controller or
the I/O from the peer device.
Solid
Green
The adapter is properly
connected and
communicating on the
network.
• No action required.