Rockwell Automation RECOMM-DNET DeviceNet Adapter for use with DPI AC Drives User Manual

Page 20

Advertising
background image

3-2

DeviceNet Adapter for use with DPI AC Drives

Step 2. Set the data rate switch as shown in figure 3.2

Setting

Description

0-63

Node address used by the adapter if switches are
enabled. The default switch setting is 63. Node
address 63 is also the default address used by all
uncommissioned devices. Do not use this address
as the final adapter address.

Important: If the Data Rate switch is set to “PGM”
(Program), the adapter will use the setting of DN
Addr Cfg (3) for the node address. The default
parameter setting is 63. Refer to chapter 4,
Configuring the DeviceNet Adapter.

64-99

Do not use. The adapter does not recognize these
addresses.

Figure 3.1 – Setting the Node Address

2

1

0

9

8

3

4

5

6

7

2

1

0

9

8

3

4

5

6

7

Tens
Digit

Ones
Digit

Setting

Description

Auto

The adapter is set to the data rate used by other
network devices. Another device on the network
must be set to a data rate.

125 K
250 K
500 K

The adapter is set to the respective data rate.

PGM

The adapter uses the setting of DN Rate Cfg (5) for
the data rate. Refer to chapter 4, Configuring the
DeviceNet Adapter.

Figure 3.2 – Setting the Data Rate

125K

250K

500K

PGM

AUTO