C.10 dpi alarm object – Rockwell Automation RECOMM-DNET DeviceNet Adapter for use with DPI AC Drives User Manual

Page 140

Advertising
background image

C-32

DeviceNet Adapter for use with DPI AC Drives

C.10 DPI Alarm Object

Class Code

Products such as SP600 drives use this object for alarms or
warnings. Adapters do not support this object.

Instances

The number of instances depends on the maximum number of
alarms supported by the queue. The maximum number of alarms
can be read in Instance 0, Attribute 2.

Class Attributes

Hexadecimal

Decimal

0x98

152

Number

Description

0

Class Attributes

1

Most Recent Alarm

2

Second Most Recent Alarm

Attribute

ID

Access

Rule

Name

Data Type

Description

1

Get

Class Revision WORD

Revision of object

2

Get

Number of
Instances

WORD

Maximum number of alarms that
the device can record in its
queue

3

Set

Alarm
Command
Write

BYTE

0 = No Operation
1 = Clear Alarm
2 = Clear Alarm Queue
3 = Reset Device

4

Get

Fault Data List

STRUCT of
BYTE
BYTE
WORD[n]

Reserved

5

Get

Number of
Recorded
Alarms

WORD

Number of alarms in the queue.
A “0” indicates the alarm queue
is empty.

Advertising