C.10 dpi alarm object – Rockwell Automation RECOMM-DNET DeviceNet Adapter for use with DPI AC Drives User Manual
Page 140

C-32
DeviceNet Adapter for use with DPI AC Drives
C.10 DPI Alarm Object
Class Code
Products such as SP600 drives use this object for alarms or
warnings. Adapters do not support this object.
Instances
The number of instances depends on the maximum number of
alarms supported by the queue. The maximum number of alarms
can be read in Instance 0, Attribute 2.
Class Attributes
Hexadecimal
Decimal
0x98
152
Number
Description
0
Class Attributes
1
Most Recent Alarm
2
Second Most Recent Alarm
…
…
Attribute
ID
Access
Rule
Name
Data Type
Description
1
Get
Class Revision WORD
Revision of object
2
Get
Number of
Instances
WORD
Maximum number of alarms that
the device can record in its
queue
3
Set
Alarm
Command
Write
BYTE
0 = No Operation
1 = Clear Alarm
2 = Clear Alarm Queue
3 = Reset Device
4
Get
Fault Data List
STRUCT of
BYTE
BYTE
WORD[n]
Reserved
5
Get
Number of
Recorded
Alarms
WORD
Number of alarms in the queue.
A “0” indicates the alarm queue
is empty.