2 setting the fault configuration parameters – Rockwell Automation RECOMM-DNET DeviceNet Adapter for use with DPI AC Drives User Manual

Page 42

Advertising
background image

4-18

DeviceNet Adapter for use with DPI AC Drives

Changes to these parameters take effect immediately. A reset is not
required.

4.9.2 Setting the Fault Configuration Parameters

If you set Comm Flt Action (10), Idle Flt Action (11), or Peer Flt
Action (34) to the “Send Flt Cfg,” the values in parameters shown in
table 4.7 are sent to the drive after a communications fault and/or
idle fault occurs. You must set these parameters to values required
by your application.

Changes to these parameters take effect immediately. A reset is not
required.

Figure 4.26 – Fault Action Screens on an LCD OIM

Port 5 Device

RECOMM-DNET

Parameter #: 10

Comm Flt Action

0

Fault

Port 5 Device

RECOMM-DNET

Parameter #: 11

Idle Flt Action

0

Fault

Table 4.7 – Fault Configuration Parameters

Parameter

Name

Description

15

Flt Cfg Logic

A 16-bit value sent to the drive for Logic
Command.

16

Flt Cfg Ref

A 32-bit value (0 – 4294967295) sent to the
drive as a Reference or Datalink.

Important: If the drive uses a 16-bit
Reference or 16-bit Datalinks, the most
significant word of the value must be set to
zero (0) or a fault will occur.

17 – 24

Flt Cfg x1 In
or Flt Cfg x2
In