4-18
DeviceNet Adapter for use with DPI AC Drives
Changes to these parameters take effect immediately. A reset is not
required.
4.9.2 Setting the Fault Configuration Parameters
If you set Comm Flt Action (10), Idle Flt Action (11), or Peer Flt
Action (34) to the “Send Flt Cfg,” the values in parameters shown in
table 4.7 are sent to the drive after a communications fault and/or
idle fault occurs. You must set these parameters to values required
by your application.
Changes to these parameters take effect immediately. A reset is not
required.
Figure 4.26 – Fault Action Screens on an LCD OIM
Port 5 Device
RECOMM-DNET
Parameter #: 10
Comm Flt Action
0
Fault
Port 5 Device
RECOMM-DNET
Parameter #: 11
Idle Flt Action
0
Fault
Table 4.7 – Fault Configuration Parameters
Parameter
Name
Description
15
Flt Cfg Logic
A 16-bit value sent to the drive for Logic
Command.
16
Flt Cfg Ref
A 32-bit value (0 – 4294967295) sent to the
drive as a Reference or Datalink.
Important: If the drive uses a 16-bit
Reference or 16-bit Datalinks, the most
significant word of the value must be set to
zero (0) or a fault will occur.
17 – 24
Flt Cfg x1 In
or Flt Cfg x2
In