DeviceNet Objects
C-21
11
Get/Set
DPI Link
BYTE[3]
Link (parameter or function
block that is the source of the
value)
(0 = no link)
12
Get
Help Object
Instance
WORD
ID for help text for this
parameter
13
Get
DPI Read
Basic
STRUCT of
BOOL[32]
CONTAINER
CONTAINER
CONTAINER
CONTAINER
STRING[16]
STRING[4]
Descriptor (Refer to pages C-
22 to C-23)
Parameter value
Minimum value
Maximum value
Default value
Parameter name
Units (e.g., Amp, Hz)
14
Get
DPI
Parameter
Name
STRING[16]
Parameter name
15
Get
DPI
Parameter
Alias
STRING[16]
Customer-supplied parameter
name.
16
Get
Parameter
Processing
Error
BYTE
0 = No error
1 = Value is less than the
minimum
2 = Value is greater than the
maximum
1
A CONTAINER is a 32-bit block of data that contains the data type used by a
parameter value. If signed, the value is sign extended. Padding is used in the
CONTAINER to ensure that it is always 32-bits.
2
This value is used in the formulas used to convert the parameter value between
display units and internal units. Refer to Formulas for Converting on page C-23.
3
Do NOT continually write parameter data to NVS. Refer to the attention on page 7.1.
Attribute
ID
Access
Rule
Name
Data Type
Description