Configuring the DeviceNet Adapter

4-7

4.4

Setting the Node Address

If the adapter Data Rate switch is set to “PGM,” the value of DN
Addr Cfg (3) determines the node address.

Step 1. Set the value of DN Addr Cfg (3) to a unique node address.

See figure 4.6. Do not use node address 63 because all
new devices use it as the default address. Address 63 is
also used for Automatic Device Replacement (ADR).

Step 2. Reset the adapter. Refer to section 4.10, Resetting the

Adapter, for this procedure.

If you are using RSNetWorx for DeviceNet, select Network > Single
Browse Path
to see the new address; then delete the old address.

Figure 4.5 – Sample SP600 Drive Dialog Box (Drive Parameters Tab)

SP600 Standard

Figure 4.6 – DeviceNet Node Address Screen on an LCD OIM

Port 5 Device

RECOMM-DNET

Parameter #: 3
DN Addr Cfg

63

0 <> 63

Default = 63