Rockwell Automation RECOMM-DNET DeviceNet Adapter for use with DPI AC Drives User Manual

Page 138

Advertising
background image

C-30

DeviceNet Adapter for use with DPI AC Drives

Instance Attributes

6

Get

Number of
Recorded Faults

WORD

Number of faults/events in the
queue. A “0” indicates the fault
queue is empty.

7

Get

Fault Parameter
Reference

WORD

Reserved

Attribute

ID

Access

Rule

Name

Data Type

Description

Attribute

ID

Access

Rule

Name

Data Type

Description

0

Get

Full/All
Information

STRUCT of
WORD
STRUCT of
BYTE
BYTE
STRING[16]
STRUCT of
LWORD

BOOL[16]

WORD
CONTAINER[n]

Fault code
Fault source
DPI port
DPI Device Object
Fault text
Fault time stamp
Timer value (0 = Timer not
supported)
BOOL[0]: (0 = invalid data,

1 = valid data)

BOOL[1]: (0 = elapsed time,

1 = real time)

BOOL[2 - 15]: Not used
Reserved
Reserved

1

Get

Basic
Information

STRUCT of
WORD
STRUCT of
BYTE
BYTE
STRUCT of
LWORD

BOOL[16]

Fault code
Fault source
DPI port
DPI Device Object
Fault time stamp
Timer value (0 = Timer not
supported)
BOOL[0]: (0 = invalid data,

1 = valid data)

BOOL[1]: (0 = elapsed time,

1 = real time)

BOOL[2 - 15]: Not used

Advertising