B-4

DeviceNet Adapter for use with DPI AC Drives

This parameter is a command. It will be reset to 0 = Ready after the
command has been performed.

Action that the adapter and drive take if the adapter detects that
DeviceNet communications have been disrupted. This setting is
effective only if I/O that controls the drive is transmitted though the
adapter.

9

Reset Module

Range:

0 = Ready (No action)
1 = Reset Module
2 = Set Defaults (Restores adapter to factory-default

settings)

Default:

0 = Ready

Type:

Read/Write

Reset Required: No

!

ATTENTION: If the adapter is transmitting I/O that
controls the drive, the drive may fault when you reset
the adapter. Determine how your drive will respond
before resetting a connected adapter. Failure to
observe this precaution could result in bodily injury
or damage to equipment.

10

Comm Flt Action

Range:

0 = Fault
1 = Stop
2 = Zero Data
3 = Hold Last
4 = Send Flt Cfg

Default:

0 = Fault

Type:

Read/Write

Reset Required: No

!

ATTENTION: Comm Flt Action (10) lets you
determine the action the adapter and connected
drive if communications are disrupted. By default,
this parameter faults the drive. You can set this
parameter so that the drive continues to run. Take
precautions to ensure that the setting of this
parameter does not create a hazard of injury or
equipment damage. Failure to observe this
precaution could result in bodily injury or damage to
equipment.