Rockwell Automation RECOMM-DNET DeviceNet Adapter for use with DPI AC Drives User Manual
Page 132

C-24
DeviceNet Adapter for use with DPI AC Drives
Format for Get_Attributes_Scattered Service
The structure shown below can get up to eight parameters in a
single message. In the Response Message, a parameter number
with the high bit set indicates that the associated parameter value
field actually contains an error code.
Request
Response
Word 0
TXID
Command
TXID
Status
1
Port
Size
Port
Size
2
Service
Address
Service
Address
3
Class
Parameter Number
4
Instance
Parameter Value LSW
5
Attribute
Parameter Value MSW
6
Parameter Number
Parameter Number
7
Pad Word
Parameter Value LSW
8
Pad Word
Parameter Value MSW
9
Parameter Number
Parameter Number
10
Pad Word
Parameter Value LSW
11
Pad Word
Parameter Value MSW
12
Parameter Number
Parameter Number
13
Pad Word
Parameter Value LSW
14
Pad Word
Parameter Value MSW
15
Parameter Number
Parameter Number
16
Pad Word
Parameter Value LSW
17
Pad Word
Parameter Value MSW
18
Parameter Number
Parameter Number
19
Pad Word
Parameter Value LSW
20
Pad Word
Parameter Value MSW
21
Parameter Number
Parameter Number
22
Pad Word
Parameter Value LSW
23
Pad Word
Parameter Value MSW
24
Parameter Number
Parameter Number
25
Pad Word
Parameter Value LSW
26
Pad Word
Parameter Value MSW
27
Parameter Number
Not Used
28
Pad Word
Not Used