5 controllogix example – Rockwell Automation RECOMM-DNET DeviceNet Adapter for use with DPI AC Drives User Manual
Page 74
Advertising
7-8
DeviceNet Adapter for use with DPI AC Drives
7.5
ControlLogix Example
The data in this example is for an SP600 drive at node address 1.
Refer to section 7.2 for a description of the content in each box.
Configuration
Value
Description
Refer to . . .
Service Code
Object Type
Object ID
Object Attribute
e (hex)
f (hex)
101 (dec)
1 (hex)
Get_Attribute_Single
Parameter Object
Parameter Address
Parameter Value
Page C-10
Page C-8
Page C-9
Figure 7.5 – Data Format for a Read and Write Parameter (1 of 2)