C.3 register object – Rockwell Automation RECOMM-DNET DeviceNet Adapter for use with DPI AC Drives User Manual

Page 114

Advertising
background image

C-6

DeviceNet Adapter for use with DPI AC Drives

C.3 Register Object

Class Code

Instances

Class Attributes

Not supported.

Hexadecimal

Decimal

0x07

7

Instance

Description

1

All polled data being read from the DPI device (read-only)

2

All polled data written to the DPI device (read/write)

3

Logic Status and Feedback data (read-only)

4

Logic Command and Reference data (read/write)

5

Datalink A (input data from device to scanner) (read only)

6

Datalink A (output data from scanner to device) (read/write)

7

Datalink B (input data from device to scanner) (read only)

8

Datalink B (output data from scanner to device) (read/write)

9

Datalink C (input data from device to scanner) (read only)

10

Datalink C (output data from scanner to device) (read/write)

11

Datalink D (input data from device to scanner) (read only)

12

Datalink D (output data from scanner to device) (read/write)

13

Logic Status and Feedback Data (read-only)

14

Mask

1

(read/write)

1

The mask command word is set to the value of the first word of the data
where there are ones in the second word of the data. Command = (word
1 and not word 2) or (word 1 and word 2). This only controls specified bits
in the Logic Command data to the DPI product and does not change the
Reference value.