Rockwell Automation RECOMM-DNET DeviceNet Adapter for use with DPI AC Drives User Manual
Page 134

C-26
DeviceNet Adapter for use with DPI AC Drives
Response Data for Get_Attributes_Scattered
Format for Set_Attributes_Scattered Service
The structure shown below can get up to eight parameters in a
single message. In the Response Message, a parameter number
with the high bit set indicates that the associated pad word field
contains an error code.
Address
Value
(hex)
Description
Refer To . . .
N30:70
0101
TXID = 01, Status = 01 (successful transaction)
Section 7.3
N30:71
0012
Port = 00, Size = 18 bytes (12 hex)
Section 7.3
N30:72
CB01
Service = CB (successful)
Section 7.3
Address = 01 (Node Address)
Section 7.3
N30:73
0001
Parameter Number 1
N30:74
0258
Value = 600 (258 hex) = 60.0 Hz
N30:75
0000
N30:76
0003
Parameter Number 3
N30:77
0001
Value = 1 (1 hex) = 0.1A
N30:78
0000
N30:79
0006
Parameter Number 6
N30:80
0864
Value = 2148 (864 hex) = 214.8V AC
N30:81
0000
Request
Response
Word 0
TXID
Command
TXID
Status
1
Port
Size
Port
Size
2
Service
Address
Service
Address
3
Class
Parameter Number
4
Instance
Pad Word or Error Code
5
Attribute
Pad Word
6
Parameter Number
Parameter Number
7
Parameter Value LSW
Pad Word or Error Code
8
Parameter Value MSW
Pad Word
9
Parameter Number
Parameter Number
10
Parameter Value LSW
Pad Word or Error Code
11
Parameter Value MSW
Pad Word