background image

DeviceNet Objects

C-7

Instance Attributes

Important:

Setting a register object attribute can only be
accomplished through a connection with a non-zero
expected packet rate (EPR). This feature is to prevent
accidental control of a DPI device.

Services

Attribute

ID

Access

Rule

Name

Data

Type

Description

1

Get

Bad Flag

BOOL

If set to 1, then attribute
4 may contain invalid,
bad or otherwise corrupt
data.
0 = good
1 = bad

2

Get

Direction

BOOL

Direction of data transfer
0 = Producer Register
1 = Consumer Register

3

Get

Size

UINT

Size of register data in
bits

4

Conditional

1

1

The access rule of Set is optional if attribute 2, Direction = 1.
If Direction = 0, the access rule is Get.

Data

ARRAY
of BITS

Data to be transferred

Service

Code

Implemented for:

Service Name

Class

Instance

0x0E

Yes

Yes

Get_Attribute_Single

0x10

No

Yes

Set_Attribute_Single