Page 34

Advertising
background image

4-10

DeviceNet Adapter for use with DPI AC Drives

Step 3. Set the bits in M-S Output (26). This parameter determines

the data transmitted from the drive to the scanner. A “1”
enables the I/O. A “0” disables the I/O. Bit 0 is the
right-most bit. In figure 4.10, it is highlighted and equals
“1.”

Step 4. Reset the adapter. Refer to section 4.10 for this procedure.

The adapter is ready to receive I/O from the master (i.e., scanner).
You must now configure the scanner to recognize and transmit I/O
to the adapter. Refer to chapter 5, Configuring the Scanner.

4.7.2 Setting an Adapter To Transmit Peer-to-Peer

Data

Step 1. Verify that Peer Out Enable (41) is set to Off. This

parameter must be set to Off while you configure some of
the peer output parameters. See figure 4.11.

Step 2. Select the source of the data to output to the network in

Peer A Output A (39). If you are transmitting a 32-bit
Reference or 32-bit Datalink, only Peer A Output will be
available. Peer B Output cannot be used. See figure 4.12.

Figure 4.10 – Master-Slave Output Screen on an LCD OIM

Bit

Description

0

Status/Feedback (Default)

1

Datalink A Output

2

Datalink B Output

3

Datalink C Output

4

Datalink D Output

5-15

Not Used

Port 5 Device

RECOMM-DNET

Parameter #: 26

M-S Output
x x x x x x x x x x x 0 0 0 0

1

Status/Fdbk

b00

Figure 4.11 – Peer Out Enable Screen on an LCD OIM

Value

Setting

0

Off (Default)

1

On

Port 5 Device

RECOMM-DNET

Parameter #: 41

Peer Out Enable

0

Off