DeviceNet Adapter Parameters

B-5

Sets the action that the adapter and the drive take if the adapter
detects that the scanner is idle because the controller was switched
to program mode. This setting is effective only if the I/O that controls
the drive is transmitted through the adapter.

Source from which the adapter node address and data rate are
taken. This will either be switches or parameters in EEPROM. It is
determined by the settings of the switches on the adapter.

11

Idle Flt Action

Range:

0 = Fault
1 = Stop
2 = Zero Data
3 = Hold Last
4 = Send Flt Cfg

Default:

0 = Fault

Type:

Read/Write

Reset Required: No

!

ATTENTION: Idle Flt Action (11) lets you determine
the action of the adapter and connected drive if the
scanner is idle. By default, this parameter faults the
drive. You can set this so that the drive continues to
run. Ensure that the setting of this parameter does
not create a hazard of injury or equipment damage.
Failure to observe this precaution could result in
bodily injury or damage to equipment.

12

DN Active Cfg

Range:

0 = EEPROM
1 = Switches

Default:

1 = Switches

Type:

Read Only

Reset Required: N/A