DeviceNet Adapter Parameters

B-11

Mask that is used for the Logic Command word when it is received
through peer input. If the mask bit is 0 (Off), the command bit is
ignored and not used. If the mask bit is 1 (On), the command bit is
checked and used.

Important: If the adapter receives a Logic Command from both a

master device and a peer device, each command bit
must have only one source. the source of command bits
set to “0” will be the Master device. The source of
command bits set to “1” will be the peer device.

Scale of the Reference received from a peer.

Important: Changes to this parameter take effect immediately. A

drive receiving its Reference from peer I/O will receive
the newly scaled Reference, resulting in a change of
speed.

32

Peer Cmd Mask

Range:

0 = Ignore bit
1 = Use bit

Default:

0000 0000 0000 0000

Type:

Read/Write

Reset Required: No

33

Peer Ref Adjust

Range:

0.00% to 199.99%

Default:

0.00%

Type:

Read/Write

Reset Required: No