Rockwell Automation RECOMM-DNET DeviceNet Adapter for use with DPI AC Drives User Manual

Page 106

Advertising
background image

B-14

DeviceNet Adapter for use with DPI AC Drives

Source of peer output data. The adapter transmits this data to the
network.

Important: These parameters can be changed only when Peer Out

Enable (41) is Off.

Important: If a 32-bit Datalink or Reference is used in Peer A

Output (39), Peer Output (40) cannot be used.

Determines if peer output is on or off.

Minimum time that a adapter will wait when transmitting to a peer.

39
40

Peer A Output
Peer B Output

Range:

0 = Off
1 = Cmd/Ref
2 = DL A Input
3 = DL B Input
4 = DL C Input
5 = DL D Input
6 = DL A Output
7 = DL B Output
8 = DL C Output
9 = DL D Output

Default:

0 = Off

Type:

Read/Write

Reset Required: No

41

Peer Out Enable

Range:

0 = Off
1 = On

Default:

0 = Off

Type:

Read/Write

Reset Required: No

42

Peer Out Time

Range:

0.01 to 10.00 seconds

Default:

10.00 seconds

Type:

Read/Write

Reset Required: No

Advertising