Rockwell Automation RECOMM-DNET DeviceNet Adapter for use with DPI AC Drives User Manual
Page 146

D-2
DeviceNet Adapter for use with DPI AC Drives
Logic Status Word
x
x
x
Reference
Select
000 = No Command
001 = Ref. 1 (Ref A Select)
010 = Reserved
011 = Ref. 3 (Preset 3)
100 = Ref. 4 (Preset 4)
101 = Ref. 5 (Preset 5)
110 = Ref. 6 (Preset 6)
111 = Ref. 7 (Preset 7)
x
MOP
Decrement
0 = Not Decrement
1 = Decrement
1
A 0 = Not Stop condition (logic 0) must first be present before a 1 = Start condition
will start the drive.
Logic Bits
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 Command
Description
Logic Bits
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Status
Description
x Ready
0 = Not Ready
1 = Ready
x
Active
0 = Not Active
1 = Active
x
Command
Direction
0 = Reverse
1 = Forward
x
Actual
Direction
0 = Reverse
1 = Forward
x
Accel
0 = Not Accelerating
1 = Accelerating
x
Decel
0 = Not Decelerating
1 = Decelerating
x
Alarm
0 = No Alarm
1 = Alarm
x
Fault
0 = No Fault
1 = Fault
x
At Speed
0 = Not At Reference
1 = At Reference
x
x
x
Local
Control
000 = Port 0 (TB)
001 = Port 1
010 = Port 2
011 = Port 3
100 = Port 4
101 = Port 5
110 = Port 6
111 = No Local