Rockwell Automation RECOMM-DNET DeviceNet Adapter for use with DPI AC Drives User Manual

Page 99

Advertising
background image

DeviceNet Adapter Parameters

B-7

Sets the Logic Command data that is sent to the drive if the
following is true:

• Comm Flt Action (10) is set to Send Flt Cfg and communications

are disrupted.

• Idle Flt Action (11) is set to Send Flt Cfg and the scanner is put

into Program or Test mode.

• Peer Flt Action (34) is set to Fault Cfg and communications are

disrupted.

The bit definitions will depend on the product to which the adapter is
connected.

Sets the Reference data that is sent to the drive if any of the
following is true:

• Comm Flt Action (10) is set to Send Flt Cfg and communications

are disrupted.

• Idle Flt Action (11) is set to Send Flt Cfg and the scanner is put

into Program mode.

• Peer Flt Action (34) is set to Fault Cfg and the scanner is put into

Program mode.

• Peer Flt Action (34) is set to Fault Cfg and communications are

disrupted.

Important: If the drive uses a 16-bit Reference, the most significant

word of this value must be set to zero (0) or a fault will
occur.

15

Flt Cfg Logic

Range:

0000 0000 0000 0000 to 1111 1111 1111 1111

Default:

0000 0000 0000 0000

Type:

Read/Write

Reset Required: No

16

Flt Cfg Ref

Range:

0 to 4294967295

Default:

0

Type:

Read/Write

Reset Required: No