4.11 Viewing the Adapter Configuration

The parameters in table 4.8 provide information about how the
adapter is configured. You can view these parameters at any time.

Table 4.8 – Adapter Configuration Status Parameters

Number

Name

Description

01

DPI Port

The port on the drive to which the adapter is
connected. Usually, it is port 5.

02

DPI Data
Rate

The data rate used by DPI in the drive. It will
be either 125 kbps or 500 kbps. It is set in the
drive, and the adapter detects it.

04

DN Addr
Actual

The node address used by the adapter. This
will be one of the following values:

• The address set by the rotary switches.

• The value of DN Addr Cfg (3) if the switches

have been disabled.

• An old address of the switches or parameter

if they have been changed and the adapter
has not been reset.

06

DN Rate
Actual

The data rate used by the adapter. This will be
one of the following values:

• The data rate set by the DIP switch.

• The value of DN Rate Cfg (5) if the switches

have been disabled.

• An old data rate of the switches or parameter

if they have been changed and the adapter
has not been reset.

07

Ref/Fdbk
Size

The size of the Reference/Feedback. It will
either be 16 bits or 32 bits. It is set in the drive
and the adapter automatically uses the correct
size.

08

Datalink
Size

The size of the Datalinks. It will either be 16
bits or 32 bits. It is set in the drive and the
adapter automatically uses the correct size.

12

DN Active
Cfg

Source from which the adapter node address
and data rate are taken. This will be either
switches or parameters in EEPROM. It is
determined by the settings of the switches on
the adapter.