DeviceNet Adapter Parameters
B-13
Timeout for a Change of State peer-to-peer connection. If the time
is reached without the adapter receiving a message, the adapter will
respond with the action specified in Peer Flt Action (34).
On the slave drive, this parameter should be set to the value
calculated from the following formula:
Peer Out Time (Master parameter 42) x Peer Out Skip (Master parameter 43)
Determines if peer input is on or off.
Status of the consumed peer input connection.
36
Peer Inp Timeout
Range:
0.01 to 180.00 seconds
Default:
10.00 seconds
Type:
Read/Write
Reset Required: No
37
Peer Inp Enable
Range:
0 = Off
1 = On
Default:
0 = Off
Type:
Read/Write
Reset Required: No
38
Peer Inp Status
Range:
0 = Off
1 = Waiting
2 = Running
3 = Faulted
Default:
0 = Off
Type:
Read Only
Reset Required: N/A