DeviceNet Adapter for use with DPI AC Drives

5.2

Setting Up the Scan List

For the scanner to communicate with a drive, the scanner must be
configured and the drive’s node number must be added to its scan
list.

Step 1. Go online with RSNetWorx for DeviceNet. Refer to section

4.3.2. The devices on the network are displayed in the
configuration view as shown in figure 5.2.

Step 2. Right-click the DeviceNet scanner (node 00 in figure 5.2

and select Properties. The Scanner Module dialog box
appears.

Important: If your scanner is an unrecognized device, you must

create an EDS file for it and then configure it. Create an
EDS file by following the instructions in section 4.3.
Configure the scanner using the General and Module
tabs. Click Help or refer to your scanner documentation
if you need more information.

Step 3. Click the Scanlist tab. A message box prompts you to

upload.

Step 4. Click Upload. Data is uploaded from the scanner, and then

the Scanlist page (figure 5.3) appears.

Step 5. Select the Automap on Add box (a check mark will

appear).

Step 6. Under Available Devices, select the drive, and then click >

(Right Arrow) to add it to the scanlist. See figure 5.3.

Figure 5.2 – Configuration View (Graph Tab)

SP600
AC Drive