4.7.3 Setting an Adapter To Receive Peer-to-Peer Data

Step 1. Verify that Peer Inp Enable (37) is set to Off. This

parameter must be set to Off while you configure some of
the peer input parameters. See figure 4.15.

Step 2. Select the node from which you want to receive data in

Peer Note to Inp (35). Valid nodes must have
RECOMM-DNET adapters connected to drives with similar
data structures. See figure 4.16.

Step 3. Select the destination of the data that is input to the drive

in Peer A Input (30). If you are receiving a 32-bit Reference
or 32-bit Datalink, only Peer A Input will be available. Peer
B Input cannot be used. See figure 4.17.

.

Figure 4.15 – Peer Input Enable Screen on an LCD OIM

Figure 4.16 – Peer Node to Input Screen on an LCD OIM

Figure 4.17 – Peer A Input Screen on an LCD OIM

Value

Setting

0

Off (Default)

1

On

Port 5 Device

RECOMM-DNET

Parameter #: 37
Peer Inp Enable

0

Off

Port 5 Device

RECOMM-DNET

Parameter #: 35
Peer Node to Inp

0

0 <>63

Default = 0

Port 5 Device

RECOMM-DNET

Parameter #: 30

Peer A Input

1

Cmd/Ref

Value

Description

0

Off (Default)

1

Logic Command/Reference

2 5

Datalink A, B, C, or D

Input