3 setting an adapter to receive peer-to-peer data – Rockwell Automation RECOMM-DNET DeviceNet Adapter for use with DPI AC Drives User Manual
Page 36

4-12
DeviceNet Adapter for use with DPI AC Drives
4.7.3 Setting an Adapter To Receive Peer-to-Peer Data
Step 1. Verify that Peer Inp Enable (37) is set to Off. This
parameter must be set to Off while you configure some of
the peer input parameters. See figure 4.15.
Step 2. Select the node from which you want to receive data in
Peer Note to Inp (35). Valid nodes must have
RECOMM-DNET adapters connected to drives with similar
data structures. See figure 4.16.
Step 3. Select the destination of the data that is input to the drive
in Peer A Input (30). If you are receiving a 32-bit Reference
or 32-bit Datalink, only Peer A Input will be available. Peer
B Input cannot be used. See figure 4.17.
.
Figure 4.15 – Peer Input Enable Screen on an LCD OIM
Figure 4.16 – Peer Node to Input Screen on an LCD OIM
Figure 4.17 – Peer A Input Screen on an LCD OIM
Value
Setting
0
Off (Default)
1
On
Port 5 Device
RECOMM-DNET
Parameter #: 37
Peer Inp Enable
0
Off
Port 5 Device
RECOMM-DNET
Parameter #: 35
Peer Node to Inp
0
0 <>63
Default = 0
Port 5 Device
RECOMM-DNET
Parameter #: 30
Peer A Input
1
Cmd/Ref
Value
Description
0
Off (Default)
1
Logic Command/Reference
2 5
Datalink A, B, C, or D
Input