Power Requirements

All switches, slow-blow fuses and power cables are customer supplied and must be chosen as
outlined by applicable national and/or local electrical codes. Installation must be performed by
qualified personnel.

Use a separate primary line disconnect switch for the power supply. Size the disconnect box to the following

requirements:

Rated Input

Input

Current @

Recommended

Voltage

Phase

30 kw Output

Slow-Blow Fuse Size

200 VAC

3

108 amps

150 amps

208 VAC

3

104 amps

150 amps

220 VAC

3

98 amps

150 amps

240 VAC

3

90 amps

150 amps

380 VAC

3

57 amps

80 amps

400 VAC

3

56 amps

80 amps

415 VAC

3

52 amps

70 amps

440 VAC

3

49 amps

70 amps

480 VAC

3

45 amps

60 amps

600 VAC

3

36 amps

50 amps

Line Disconnect Switch

The line disconnect switch serves as the supply voltage disconnecting (isolating) device. Install this switch on

a wall near the power supply for easy accessibility by the operator.

The line disconnect switch must be

installed by qualified personnel following all applicable local and national codes. The switch should:

• Isolate the electrical equipment and disconnect all live conductors from the supply voltage when in "OFF"

position

• Have one "OFF" and one "ON" position clearly marked with "0" (OFF) and "1" (ON)

• Have an external operating handle capable of being locked in the "OFF" position

• Contain a power operated mechanism that serves as an emergency stop

• Have slow-blow fuses installed for the proper breaking capacity (see table above)

Power Cable

Power Source to Power Supply

Wire sizes vary based on the distance of the receptacle from the main box. The wire sizes listed on the

following page were taken from the National Electric Code 1990 handbook, table 310.16.

Use a 4-conductor