MP940 Functions
4.2.8 General-purpose Serial Definitions
4-20
General-purpose Serial Parameter Default Values
The following table shows the default values for the general-purpose serial parameters.
Item
CIR01
CIR02
Rack No.
01
01
Slot No.
02
02
Circuit No.
01
02
Transmission Protocol
MEMOBUS
MEMOBUS
Master/Slave
Slave
Slave
Device Address
01
02
Serial Interface
RS-232C
RS-485
Transmission Mode
RTU
RTU
Data Length
8 bits
8 bits
Parity Bits
Even
Even
Stop Bits
1
1
Baud Rate
9,600 bps
9,600 bps
Transmission Delay
Not designated.
Not designated.
Automatic Reception
Not designated.
Not designated.
Input Relay Read
IW0000/2048
IW0000/2048
Input Register Read
IW0000/2048
IW0000/2048
Coil Read/Write
MW00000/32768
MW00000/32768
Holding Register Read/
Write
MW00000/32768
MW00000/32768
Coil/Holding Register
Write Range
MW00000/32767
MW00000/32767