A.03, Display and outputs, Status and remedy for alarm – Yaskawa MP940 User Manual
Page 373: A.04

SERVOPACK Inspection, Maintenance, and Troubleshooting
10.2.1 Troubleshooting Problems with Alarm Displays
10-6
A.03
A.03: Main Circuit Encoder Error
Display and Outputs
Note: OFF: Output transistor is OFF (alarm state).
Status and Remedy for Alarm
A.04
A.04: Parameter Setting Error
Display and Outputs
Note: OFF: Output transistor is OFF (alarm state)
Status and Remedy for Alarm
Alarm Outputs
Alarm Code Outputs
ALM Output
ALO1
ALO2
ALO3
OFF
OFF
OFF
OFF
Cause
Remedy
A
Circuit board (1PWB or 2PWB) defective.
Replace SERVOPACK.
Alarm Outputs
Alarm Code Outputs
ALM Output
ALO1
ALO2
ALO3
OFF
OFF
OFF
OFF
Cause
Remedy
A
An out-of-range parameter was previ-
ously set or loaded.
• Reset all parameters in range.
• Otherwise, re-load correct parameter.
B
Circuit board (1PWB) defective.
Replace SERVOPACK.
A
At power ON
A, B
At power ON