A.40, Display and outputs, Status and remedy for alarm – Yaskawa MP940 User Manual
Page 377: A.41

SERVOPACK Inspection, Maintenance, and Troubleshooting
10.2.1 Troubleshooting Problems with Alarm Displays
10-10
A.40
A.40: Main Circuit DC Voltage Error Detected: Overvoltage
Display and Outputs
Note: OFF: Output transistor is OFF (alarm state).
ON: Output transistor is ON.
Status and Remedy for Alarm
A.41
A.41: Main Circuit Voltage Error Detected: Undervoltage
Display and Outputs
Note: OFF: Output transistor is OFF (alarm state).
ON: Output transistor is ON.
Alarm Outputs
Alarm Code Outputs
ALM Output
ALO1
ALO2
ALO3
OFF
OFF
ON
OFF
Cause
Remedy
A
The power supply voltage is not within
the range of specifications.
Check power supply.
B
Load exceeds capacity of the Regener-
ative Unit.
Check specifications of load moment
of inertia and overhanging load.
C
Regenerative transistor is abnormal.
Replace SERVOPACK.
D
Rectifying diode defective.
E
SERVOPACK defective.
Alarm Outputs
Alarm Code Outputs
ALM Output
ALO1
ALO2
ALO3
OFF
OFF
ON
OFF
E
A, B, C, D
A, D
During servomotor
operation
Occurred when main cir-
cuit power turned ON.
Occurred when the con-
trol power turned ON.