3 opening the local i/o definition window, Analog output – Yaskawa MP940 User Manual
Page 119
Advertising
MP940 Functions
4.3.3 Opening the Local I/O Definition Window
4-26
Analog Output
∗
Analog output linearity is only assured between –10.0 and 10.0 (V).
4.3.3 Opening the Local I/O Definition Window
The Local I/O Definition Window is opened from the Module Configuration Definition
Window. Refer to the sections on opening individual Module Definition Windows.
Item
Contents
D/A Output
Command
Output Range
16 bits
0 to ± 10 V
Output Charac-
teristics*
V data = Output register data
10.75/32,767
Output register data = V data 32,767/10.75
Analog Output
Circuit
Register
Number
OW0001 (default): Can be set on the Module Configuration Definition Screen.
32767
-32768
+10.75
-10.75
V
+10
30480
-30481
-10
×
×
47 Ω
1 kΩ
-
+
+15 V
-15 V
1
26
L
P
External device
-10 to 10 V
Advertising