Status and remedy for alarm, A.32, Display and outputs – Yaskawa MP940 User Manual
Page 376

10.2 Troubleshooting
10-9
10
Status and Remedy for Alarm
A.32
A.32: Regenerative Overload
Display and Outputs
Note: OFF: Output transistor is OFF (alarm state).
ON: Output transistor is ON.
Status and Remedy for Alarm
Cause
Remedy
A
Regenerative transistor is abnormal.
Replace SERVOPACK.
B
Disconnection of the regenerative
resistor.
Replace SERVOPACK or regenera-
tive resistor.
C
Regenerative Unit disconnected
(for an external regenerative resistor).
Check wiring of the external regener-
ative resistor.
D
SERVOPACK defective.
Replace SERVOPACK.
Alarm Outputs
Alarm Code Outputs
ALM Output
ALO1
ALO2
ALO3
ON
ON
OFF
OFF
Cause
Remedy
A
Regenerative power exceeds the allowable
value.
Use an external regenerative resistor
that matches the regenerative power
capacity.
B
Alarm occurs although an external regener-
ative resistor is used and the temperature
rise of the regenerative resistor is small.
Correct parameter Pn600.
A.B
A.B.C
D
During servomotor
operation
Occurred approximately
1 second after the main
circuit power ON.
Occurred when the
control power turned
ON
A, B
A, B, C
A, B
During servomotor
operation