Status and remedy for alarm, A.c1, Display and outputs – Yaskawa MP940 User Manual
Page 389

SERVOPACK Inspection, Maintenance, and Troubleshooting
10.2.1 Troubleshooting Problems with Alarm Displays
10-22
Status and Remedy for Alarm
A.C1
A.C1: Servo Overrun
Display and Outputs
Note: OFF: Output transistor is OFF (alarm state).
ON: Output transistor is ON.
Status and Remedy for Alarm
Cause
Remedy
A
Error in reference read-in unit (A/D
Converter, etc.).
Reset alarm and restart operation.
B
Reference read-in unit faulty (A/D
Converter, etc.).
Replace SERVOPACK.
C
Circuit board (1PWB) defective.
Replace SERVOPACK.
Alarm Outputs
Alarm Code Outputs
ALM Output
ALO1
ALO2
ALO3
ON
OFF
ON
OFF
Cause
Remedy
A
Servomotor wiring incorrect or dis-
connected.
Check wiring and connectors at servomo-
tor.
B
Encoder wiring incorrect or discon-
nected.
Check wiring and connectors at encoder.
C
Encoder defective.
Replace servomotor.
D
Circuit board (1PWB) defective.
Replace SERVOPACK.
C
A,B
During servomotor
operation
At power ON
D
A,B,C,D
A,B,C
A,B,C,D
At power ON
Parameter
Pn50A.1 = 7
Occurred 1 to 3 seconds
after power ON
Parameter
Pn50A.1 = Other
than “7"
When servo ON (/S-ON)
signal turned ON
On speed reference input