Status and remedy for alarm, A.e1, Display and outputs – Yaskawa MP940 User Manual
Page 394: A.e2

10.2 Troubleshooting
10-27
10
Status and Remedy for Alarm
A.E1
A.E1: Option Timeout
Display and Outputs
Note: OFF: Output transistor is OFF (alarm state).
ON: Output transistor is ON.
Status and Remedy for Alarm
A.E2
A.E2: Option WDC Error
Display and Outputs
Note: OFF:Output transistor is OFF (alarm state).
ON:Output transistor is ON.
Cause
Remedy
A
• No MP940 Module is mounted, or
MP940 is defective.
• There is no 24-VDC power supply
to the MP940.
• User program error
• Supply a 24-VDC power supply to the
MP940.
• Correct the MP940 user program.
• Initialize the MP940 Module’s memory.
• Replace the MP940 Module.
Alarm Outputs
Alarm Code Outputs
ALM Output
ALO1
ALO2
ALO3
OFF
ON
ON
OFF
Cause
Remedy
A
Option Unit is defective.
Replace the Option Unit.
Alarm Outputs
Alarm Code Outputs
ALM Output
ALO1
ALO2
ALO3
OFF
ON
ON
OFF
A
At power ON
A
At power ON