5 power supply connector cable, Power supply connector (power), V input cable preparing procedure – Yaskawa MP940 User Manual

Page 197

Advertising
background image

5.3 Connection Methods

5-25

5

5.3.5 Power Supply Connector Cable

„

Power Supply Connector (POWER)

The MP940 Module must be supplied with a 24-VDC power supply.

The connector is a screw-locking terminal block connector (BL3.5/3F-AU, manufactured by
Weidmüler).

„

24-V Input Cable Preparing Procedure

Use a twisted-pair cable with a wire size of AWG #24 to AWG #20 (0.2 mm

2

to 0.51 mm

2

)

when connecting the 24-VDC power supply and MP940 Module power supply connector.

Prepare a cable using the following procedure.

1. Strip the wire of its covering.

Strip the wire of its covering for 6.5 mm from the head.

2. Insert the wire to a plug.

Insert the core wire deeply into the plug and tighten the screws with a 0.3 to 0.4 Nm fas-
tening torque.

Pin No.

Signal

Name

Name

3

+24 V

+24-VDC input

2

GND

0 V

1

FG

POWER

+24V

GND

FG

Pin No.

Signal Name

Name

3

+24 V

+24-VDC input

2

GND

GND

1

FG

FG

6.5 mm

Core wire

Covering

+

+ side (Pin No. 4)

– side (Pin No. 2)

Advertising