Status and Remedy for Alarm
A.7A
A.7A: Heat Sink Overheated
Display and Outputs
Note: OFF: Output transistor is OFF (alarm state).
ON: Output transistor is ON.
Status and Remedy for Alarm
Note: This alarm display tends to occur only with a SERVOPACK of 30 W
to 1000 W.
Cause
Remedy
A
Frequently turning the main circuit power
ON/OFF.
Do not repeatedly turn ON/OFF the main
circuit power.
B
Circuit board (1PWB) defective.
Replace SERVOPACK.
Alarm Outputs
Alarm Code Outputs
ALM Output
ALO1
ALO2
ALO3
ON
ON
ON
OFF
Cause
Remedy
A
The ambient temperature of the SERVO-
PACK exceeds 55ºC.
Alter conditions so that the ambient
temperature goes below 55ºC.
B
The air flow around the heat sink is bad.
Follow installation methods and pro-
vide sufficient space as specified.
C
Fan stopped.
Replace SERVOPACK.
D
SERVOPACK is operating under over-
load.
Reduce load.
E
SERVOPACK defective
Replace SERVOPACK.