A.CC
A.CC: Multi-turn Limit Disagreement Alarm
Display and Outputs
Note: OFF: Output transistor is OFF (alarm state).
ON: Output transistor is ON.
Status and Remedy for Alarm
A.d0
A.d0: Position Error Pulse Overflow
Display and Outputs
Note: OFF: Output transistor is OFF (alarm state).
ON: Output transistor is ON.
Alarm Outputs
Alarm Code Outputs
ALM Output
ALO1
ALO2
ALO3
ON
OFF
ON
OFF
Cause
Remedy
A
The setting of the Multi-turn Limit
Setting (Pn205) parameter in the
SERVOPACK is incorrect.
Change parameter Pn205.
B
The multi-turn limit has not been set
in the encoder.
Check to be sure the Multi-turn
Limit Setting (Pn205) parameter in
the SERVOPACK is correct, create a
Multi-turn Limit Disagreement
Alarm (A.CC), and then execute the
encoder multi-turn limit setting
change (Fn013).