2 troubleshooting, 1 troubleshooting problems with alarm displays – Yaskawa MP940 User Manual
Page 372

10.2 Troubleshooting
10-5
10
10.2 Troubleshooting
This section describes causes and remedies for problems which cause an alarm display and for
problems which result in no alarm display.
10.2.1 Troubleshooting Problems with Alarm Displays
Problems that occur in the Servodrivers are displayed on the panel operator as “A.
" or
“CPF
". “A.- -”, however, does not indicate an alarm. Refer to the following sections to
identify the cause of an alarm and the action to be taken.
Contact your Yaskawa representative if the problem cannot be solved by the described pro-
cedures.
A.02
A.02: Parameters Breakdown
Display and Outputs
Note: OFF: Output transistor is OFF (alarm state).
Status and Remedy for Alarm
Alarm Outputs
Alarm Code Outputs
ALM Output
ALO1
ALO2
ALO3
OFF
OFF
OFF
OFF
Cause
Remedy
A
Power turned OFF during parameter write.
Alarm occurred at next power ON.
Replace SERVOPACK.
B
Circuit board (1PWB) defective.
Replace SERVOPACK.
A, B
At power ON