HP 30 HP30 User Manual

Page 101

Advertising
background image

Chapter 6 - Parameter description [FU1]

6-17




FU1-38: Output Voltage Adjustment






This function is used to adjust the output voltage of the
inverter. This is useful when using a motor with a lower
rated voltage than the main input voltage. When this is set
at 100%, inverter outputs its rated voltage.












Note: The inverter output voltage does not

exceed the main input voltage, even though FU1-
38 is set at 110%.


FU1-39: Energy Save Level






This function is used to reduce the output voltage in
applications that do not require high torque and current at
its steady speed. The inverter reduces its output voltage
after accelerating to the reference frequency (steady
speed) if the energy save level is set at 20%. This function
may cause over-current trip due to the lack of output
torque in a fluctuating load.
This function does not work with 0% set point value.










[When Energy Save Level is set at 20%]


Note: This function is not recommended for a large load or

for an application that need frequent acceleration and
deceleration.

Note: This function does not work when ‘Sensorless’ is

selected in FU2-40 [Control Mode].


FU1-50: Electronic Thermal (Motor i

2

t) Selection

FU1-51: Electronic Thermal Level for 1 Minute
FU1-52: Electronic Thermal Level for Continuous
FU1-53: Electronic Thermal Characteristic (Motor
type) selection


These functions are to protect the motor from overheating
without using additional thermal overload relay. Inverter
calculates the temperature rising of the motor using
several parameters and determines whether or not the
motor is overheated. Inverter will turn off its output and
display a trip message when the electronic thermal feature
is activated.






This function activates the ETH parameters by setting
‘Yes’.





This is the reference current when the inverter determines

Related Functions: FU1-21 [Base Frequency]

FU1-22 [Starting Frequency]

FU1-29

[Volts/Hz

Pattern]

FU1

►Volt control

38 100.0 %

100

38

Factory Default:

100.0 %

100

Output Voltage

Output
Frequency

FU1-21 [Base Freq]

100%

50%

When set at 50%

FU1

► Energy save

39 0 %

0

39

Factory Default:

0 %

0

Output Voltage

Output
Frequency

Reference Frequency
(Steady Speed)

100%

80%

FU1

► ETH select

50 --- No ---

0

50

Factory Default:

No

0

FU1

► ETH 1min

51 150 %

150

51

Factory Default:

150 %

150