HP 30 HP30 User Manual

Page 176

Advertising
background image

Chapter 7 - Options

7-14

7.4.3

Terminals Configuration (10 pins + 14 pins)

Q1 Q2 EXTG NC P4 P5 P6 CM

NC V2 VR 5G NC NC

7.4.4 Terminal

Descriptions

Section

Terminal

Termianl name

Terminal description

P4,P5,P6 Multi-Function

Input

Used as the extended function of P1, P2, P3.
(I/O-12 ~ I/O-14).

Contact Input

CM

Common Terminal

Common terminal for P4, P5, P6

VR

Power supply for V2

DC voltage output terminal for V2 (+12V, 10mA)

V2

Analog Voltage Input

Sets the frequency by applying DC 0~10V.
Input resistor: 20 kΩ

Input

Analog

Frequency

Reference

5G

Common Terminal

Common terminal for VR and V2

LM Load

Meter

Used to monitor one of Output Frequency, Output Current,
Output Voltage, DC link Voltage. Factory setting: Output
frequency. Output voltage: 0~10V, Output current: 1mA
Preset freq: 500Hz

+15V Pulse

Output

CM

Common Terminal

Common terminal for LM

Q1,Q2

Multi-Function Output

(Open-Collect Output)

Used as the extended function of AXA, AXC (I/O-44)
Below DC 25V, 50mA

Output

Open Collector

Output

EXTG

External Common Terminal Common terminal for Q1, Q2.

NC

-

Not

used.

FG GND +5V +15V AOC BOC A+ A- B+ B-

Section

Terminal

Termianl name

Terminal description

AOC

A Pulse Input Terminal

Connects A signal of Open Collector type encoder

Open
Collector

BOC

B Pulse Input Terminal

Connects B signal of Open Collector type encoder

A+

A+ Pulse Input Terminal

Connects A+ signal of Line Drive type encoder

A-

A- Pulse Input Terminal

Connects A- signal of Line Drive type encoder

B+

B+ Pulse Input Terminal

Connects B+ signal of Line Drive type encoder

Encoder
input
signal

Line Drive

B-

B- Pulse Input Terminal

Connects B- signal of Line Drive type encoder

+5V

+5V DC Input Terminal

Provides +5V DC power output to encoder
(5V DC, Minimum 0.5A)

+15V

+15V DC Input/Output

Terminal

Provides 15V DC Input/output Terminal from External Power

Supply to Encoder (For Open collector type)

Power supply

GND

Common for Encoder

Input/output

Common terminal connecting encoder input/output signal

Grouding

FG

Ground Termnal

Used to connect shield of encoder signal

Advertising