CHAPTER 4 -

VARIOUS FUNCTION SETTING & DESCRIPTION

4.1 Function Setting


4.1.1

Basic function parameter setting


It is the basic function setting. All settings are factory defaults unless users make change. It is recommended to use factory
setting value unless the parameter change is necessary.

1) Common parameter setting
The following table shows common parameter setting that should be checked before use but making change does not
affect inverter control type.

Parameter Name

Code

Description

Rated Motor

Selection

FU2-30

Select motor and voltage rating suitable to the desired
inverter

Parameters related to

motor

FU2-31 ~ 36

Basic parameter value setting when selecting the motor
rating.
Note) If there is any discrepancy between parameter
preset value and the actual motor parameter value,
change the parameter value according to the actual
motor.

Drive Mode

DRV-3

Operation via Keypad, Fx/Rx-1, Fx/Rx-2 setting enable

Frequency

or

Torque Mode

DRV-4

Frequency/Torque setting parameter
It automatically changes to torque mode when FU2 39-
[Control mode] is set to Sensorless_T, Vector_TRQ

Accel/Decel time

setting

DRV-1, DRV-2

Setting Accel/Decel time enable

2) V/f control

FU2-39 [Control mode] is set to 0 (V/F) as factory setting. Operation via V/F control can be performed after
common parameter settings are done and the followings are set.

Parameter Name

Code

Description

Starting freq.

FU1-22

Setting frequency to start the motor

Torque boost

FU1-26

Manual or Auto torque boost settable in this parameter

Torque boost value in

FWD/REV

FU1-27, FU1-28

If FU1-26 [torque boost] is set to manual, user sets the
desired value and the direction in code FU1-27 and 28.