Chapter 6 - Parameter Description [EXT]

6-57

EXT-24: Slip Frequency for ‘Sub-B’ Board






This is the limit frequency the inverter uses to compensate
the motor speed drop due to load fluctuation. The set point
value is the percentage of FUN-32 [Rated Motor Slip].

EXT-25: P Gain for Sensored Vector_SPD
EXT-25: I Gain for Sensored Vector_SPD
EXT-27: Forward Torque Limit
EXT-28: Reverse Torque Limit









EXT-30 ~ EXT-32: Multi-Function Output Terminal
(Q1, Q2, Q3) Define – Sub-A, Sub-C


Q1, Q2, Q3 terminals are provided on Sub-A and Sub-C
board as an open collector output. The functions of these
terminals can be selected the same as I/O-44 [Multi-
function Auxiliary Contact Output Define].


























EXT-34: LM (Load Meter) Output – Sub-A
EXT-35: LM Adjustment











Load meter displays the inverter output Frequency,
Current, Voltage and DC link voltage with pulse signals on
the LM terminal of Sub-A board. The average ranges from
0V to 10V. EXT-35 is used to adjust the LM value.


[Frequency]
LM terminal outputs inverter output frequency. The output
value is determined by,
LM Output Voltage = (Output freq. / Max. freq.) × 10V ×
EXT-35 / 100

EXT

►PG Slip Freq

24 100 %

100

24

Factory Default:

100 %

100

EXT

► Q1 define

30 FDT-1

0

30

Factory Default:

FDT-1

0

EXT

► Q2 define

31 FDT-2

1

31

Factory Default:

FDT-2

1

EXT

► Q3 define

32 FDT-3

2

32

Factory Default:

FDT-3

2

EXT

► LM mode

34 Current

1

34

Factory Default:

Current

1

EXT

► LM Adjust

35 100 %

100

35

Factory Default:

100 %

100

Related Functions: FU1-54 [Overload Warning Level]

FU1-55 [Overload Warning Time]

FU1-59 [Stall Prevention Mode]

FU1-60 [Stall Prevention Level]

I/O-12 ~ I/O-14 [Multi-function Input

Terminal

define]

I/O-42 ~ I/O-43 [Frequency Detection]

I/O-44 [Multi-function Auxiliary Contact

Output

define]

I/O-50 ~ I/O-56 [Auto Operation]

EXT

► ASR P-gain

25 100 %

150

25

Factory Default:

150 %

150

EXT

► ASR I-gain

26 200 ms

200

26

Factory Default:

200 ms

200

EXT

► TRQ + Limit

27 100 %

150

27

Factory Default:

150 %

150

EXT

► TRQ – Limit

28 100 %

150

28

Factory Default:

150 %

150