Chapter 6 - Parameter description [FU1]

6-9

6.2 Function 1 Group [FU1]

FU1-00: Jump to Desired Code #






Jumping directly to any parameter code can be
accomplished by entering the desired code number. This
code is available only with LCD keypad.

FU1-03: Run Prevention






This function prevents reverse operation of the motor. This
function may be used for loads that rotate only in one
direction such as fans and pumps.

Setting Range

LCD 7-Seg

Description

None

0

Forward and Reverse run is available.

Forward Prev

1

Forward run is prevented.

Reverse Prev

2

Reverse run is prevented.


FU1-05: Acceleration Pattern
FU1-06: Deceleration Pattern









Different combinations of acceleration and deceleration
patterns can be selected according to the application.

Setting Range

LCD 7-Seg

Description

Linear

0

This is a general pattern for constant

torque applications.

S-curve

1

This pattern allows the motor to
accelerate and decelerate smoothly. The

actual acceleration and deceleration time
takes longer- about 40% than the time set

in DRV-01 and DRV-02.
This setting prevents shock during
acceleration and deceleration, and

prevents objects from swinging on
conveyors or other moving equipment.

U-curve

2

This pattern provides more efficient

control of acceleration and deceleration in
typical winding machine applications.

Minimum

3

The inverter makes shorten the
acceleration time by accelerating with a
current rate of about 150% of its rated

current and reduces the deceleration time
by decelerating with a DC voltage rate of

95% of its over-voltage trip level.
Appropriate application: When the
maximum capability of the inverter and

the motor are required.
Inappropriate application: The current

limit function may operate for a long
period of time for loads that have high

inertia such as fans.

Optimum

4

The inverter accelerates with a current
rate of about 120% of its rated current

and decelerates with a DC voltage rate of
93% of its over-voltage trip level.


Note: In case of selecting the ‘Minimum’ or ‘Optimum’, the

DRV-01 and DRV-02 is ignored.

Note: ‘Minimum’ and ‘Optimum’ functions operate normally

when the load inertia is less than 10 times compared to the
motor inertia. (FU2-37)

Note: ‘Optimum’ is useful when the motor capacity is

smaller than the inverter capacity.

Note: ‘Minimum’ and ‘Optimum’ functions are not

appropriate for down operation in an elevator application.


FU1

► Jump code

00 1

Factory Default:

1

FU1

► Run prev.

03 None

0

03

Factory Default:

None

0

FU1

►Acc. pattern

05 Linear

0

05

Factory Default:

Linear

0

FU1

►Dec. pattern

06 Linear

0

06

Factory Default:

Linear

0