HP 30 HP30 User Manual

Page 136

Advertising
background image

Chapter 6 - Parameter Description [I/O]

6-44

[Current]
FM terminal outputs inverter output current. The output
value is determined by,
FM Output Voltage = (Output current / Rated current) ×
10V × IO-41 / 150

[Voltage]
FM terminal outputs inverter output voltage. The output
value is determined by,
FM Output Voltage = (Output voltage / Max. output
voltage) × 10V × IO-41 / 100

[DC link vtg]
FM terminal outputs the DC link voltage of inverter. The
output value is determined by,
FM Output Voltage = (DC link voltage / Max. DC link
voltage) × 10V × IO-41 / 100









[FM Output (FM-CM terminal)]

[Torque]
FM terminal outputs the torque of inverter. The output
value is determined by
FM Output Voltage = (Torque current / Max.Torque
current) × 10V × IO-41 / 150


Note : 1. Max output voltage : 200V class -> 220V

400V class -> 440V
2. Max DC link voltage : 200V class -> 400V
400V class -> 800V
3. Refer to chapter 2 Specification for inverter rated current.


I/O-42: FDT (Frequency Detection) Level
I/O-43: FDT Bandwidth











These functions are used in I/O-44 [Multi-function Auxiliary
Contact Output]. See [FDT-#] in I/O-44.



I/O-44: Multi-function Auxiliary Contact Output
define (AXA-AXC)






The auxiliary contact works (Close) when the defined
condition has occurred.

Setting Range

LCD 7-Seg

Description

FDT-1

0

Output frequency arrival detection

FDT-2

1

Specific frequency level detection

FDT-3

2

Frequency detection with pulse

FDT-4

3

Frequency detection with contact
closure

FDT-5

4

Frequency detection with contact
closure (inverted FDT-4)

OL

5

Overload detection

IOL

6

Inverter overload detection

Stall

7

Stall prevention mode detection

OV

8

Over voltage detection

LV

9

Low voltage detection

OH

10

Overheat detection

I/O

► FDT freq

42 30.00 Hz

30.00

42

Factory Default:

30.00 Hz

30.00

I/O

► FDT band

43 10.00 Hz

10.00

43

Factory Default: 10.00

Hz

10.00

Related Functions: I/O-44 [Multi-function Auxiliary Output]

I/O

► Aux mode

44 Run

Factory Default:

Run

12

FM Terminal Output

Time

15Vpeak

Avg. 0~10V

500Hz, 2msec (fixed)

12

44

I/O-40

10

V

0 %

100

I/O-41 * 10 V

FM-5G

Output V

Advertising