HP 30 HP30 User Manual

Page 118

Advertising
background image

Chapter 6 - Parameter Description [FU2]

6-26






SL I-gain is the integral gain of speed controller. If this
value is set low, you can get better transient response
characteristic and steady state characteristic. However, if
this value is set too low, there may be an overshoot in
speed control.

Note: The response time of a system is affected by the load

inertia. For better control performance, set the FU2-37
[Load Inertia] correctly.





FU2-47: PID Operation Selection






This code selects the PID control.
For HVAC or Pump applications, the PID control can be
used to adjust the actual output by comparing a feedback
with a ‘Set-point’ given to the inverter. This ‘Set-point’ can
be in the form of Speed, Temperature, Pressure, Flow
level, etc. The ‘Set-point’ and the feedback signals are
provided externally to the inverter analog input terminals
V1, V2 or I. The inverter compares the signals in
calculating ‘total-error’ which is reflected in the inverter
output.
Please see FU2-50 to FU2-54 for more detail.

Note: PID control can be bypassed to manual operation

temporarily by defining one of the multifunction input
terminals (P1~P3) to “Open-loop”. The inverter will change
to manual operation from PID control when this terminal is
ON, and change back to PID control when this terminal is
OFF.









FU2-48: PID Reference Frequency Selection
FU2-49: PID Reference Mode Selection
FU2-50: PID Output Direction Selection







This code selects reference frequency for PID control.

[Ramp Freq]: PID control references frequency with Accel
and Decel pattern and time.

[Target Freq]: PID control references frequency without
Accel and Decel pattern and time.





This code selects reference input for PID control.

[Freq Mode]: PID control references signal set in DRV-04.
When selected other than ‘Freq mode’, PID control
references the selected signal regardless the selection in
DRV-04.





This code selects the direction of output value of PID
controller. The output value is added to reference
frequency.

FU2

► SL I-gain

46 3276

3276

46

Factory Default:

3276

3276

Related Functions: FU2-30 ~ FU2-37 [Motor Parameters]

FU2-40 [Control Method]

FU2

►Proc PI mode

47 --- No ---

0

47

Factory Default:

No

0

Related Functions: DRV-04 [Frequency Mode]

I/O-01 to I/O-10 [Analog Signal Setting]

I/O-12 to I/O-14 [Multi-Function Input]

EXT-15 to EXT-21 [Pulse Input Setting]

FU2-50 to FU2-54 [PID Feedback]

FU2

► PID Ref

48 Ramp freq.

0

48

Factory Default:

No

0

FU2

►PID Ref Mode

49 Freq mode

0

49

Factory Default:

Freq mode

0

FU2

► PID Out Dir

50 Ramp Freq.

0

50

Factory Default:

Ramp Freq.

0

Advertising