HP 30 HP30 User Manual

Page 155

Advertising
background image

Chapter 6 - Parameter Description [APP]

6-63

motors including main motor. For mode ‘2’, external
sequence (Refer to APP-26) should be configured.

♦ Abnormal motor can be skipped from running by using

the multi-function input terminals (P1, P2, P3, and P4). If a
multi-function terminal is opened, the inverter stops all
running motors and restarts operation with only normal
motors except the abnormal motor. (Refer to APP-29)

♦ Sleep function is initiated when flow demand is low.

Inverter stops motor when the motor runs below Sleep
Frequency (APP-24) during Sleep Delay Time (APP-23).
While in the sleep state, inverter keeps monitoring and
initiates Wake-Up function when the real value of the
controlling amount has decreased below the Wake-Up
level (APP-25).

Note: Only one auxiliary motor can be connected with AUX

terminal on control terminal strip without using MMC Option
Board.






















[MMC Diagram]

[Draw]: This is a kind of Open-Loop Tension Control. This
is used to maintain constant tension of material with the
speed difference between main motor and subordinate
motor.






APP-02: Traverse Amplitude






This code sets the frequency amplitude of traverse
operation. The value is the percentage of reference
frequency. The output value is determined by,
Trv. Amp Frequency = (Reference Freq. * Trv. Amp)/100

APP-03: Traverse Scramble Amplitude






This code sets the frequency amplitude of scramble
operation. The output value is determined by,
Trv. Scr Frequency = (Trv. Amp Frequency * (100 - Trv.

Scr))/100

APP-04: Traverse Accel Time
APP-05: Traverse Decel Time










APP

►Trv. Amp[%]

02 0.0%

0.0

02

Factory Default: 0.0%

0.0

APP

►Trv. Scr[%]

03 0.0%

0.0

03

Factory Default: 0.0%

0.0

APP

►Trv Acc Time

04 2.0 sec

2.0

04

Factory Default: 2.0

sec

2.0

APP

►Trv Dec Time

05 3.0 sec

3.0

05

Factory Default: 3.0

sec

3.0

Related Functions: APP-08 to APP-31 [MMC Parameters]

DRV-04 [Frequency Mode]

FU2-47 [PID Operation Selection]

I/O-01 to I/O-10 [Analog Signal Input]

EXT 15 to EXT21 [Pulse Input Signal]

I/O-12 to I/O-14 [Multi-Function Input]

EXT-30 to EXT-32 [Multi-Function Output]

Related Functions: APP-32 to APP-33 [Draw Parameters]

DRV-04 [Frequency Mode]

I/O-01 to I/O-10 [Analog Signal Input]

EXT 06 to EXT-10 [Analog Input Setting]

I/O-12 to I/O-14 [Multi-Function Input]

EXT-02 to EXT-04 [Multi-Function Input]

V1
V2
I

M1

M2

M3

M4

M

ACti

M

Input

Power

Main Motor

Aux. Motor 4

Aux. Motor 3

Aux. Motor 2

Aux. Motor 1

MMC Board

AUX

RLY1

RLY2

RLY3

Advertising