Chapter 1 - Installation

1-13

1.8 Control Terminals

P1 P2 P3 FX RX NC VR V1

30A 30C 30B AXA AXC

JOG CM CM BX RST I FM 5G


Type

Symbol

Name

Description

P1, P2, P3

Multi-Function Input
1, 2, 3

Used for Multi-Function Input Terminal.
(Factory default is set to “Step Frequency 1, 2, 3”.)

FX

Forward Run Command

Forward Run When Closed and Stopped When Open.

RX

Reverse Run Command

Reverse Run When Closed and Stopped When Open.

JOG

Jog Frequency
Reference

Runs at Jog Frequency when the Jog Signal is ON. The Direction is set by
the FX (or RX) Signal.

BX Emergency

Stop

When the BX Signal is ON the Output of the Inverter is Turned Off. When
Motor uses an Electrical Brake to Stop, BX is used to Turn Off the Output
Signal. When BX Signal is OFF (Not Turned Off by Latching) and FX Signal
(or RX Signal) is ON, Motor continues to Run.

RST

Fault Reset

Used for Fault Reset.

St

arting Contact Function

Se

lect

CM

Sequence Common

Common Terminal for Contact Inputs.

NC -

Not

Used.

VR

Frequency Setting Power
(+12V)

Used as Power for Analog Frequency Setting.
Maximum Output is +12V, 100mA.

V1

Frequency Reference
(Voltage)

Used for 0-10V Input Frequency Reference. Input Resistance is 20 KΩ

I

Frequency Reference
(Current)

Used for 4-20mA Input Frequency Reference. Input Resistance is 250 Ω

Input signal

Analog frequency setting

5G

Frequency Setting
Common Terminal

Common Terminal for Analog Frequency Reference Signal and FM
(Frequency Meter).

Analog

FM

Analog Output (0~10V)
(For External Monitoring)

Outputs One of the Following: Output Frequency, Output Current, Output
Voltage, DC Link Voltage and Torque. Default is set to Output Frequency.
Maximum Output Voltage and Output Current are 0-12V and 1mA.

30A
30C
30B

Fault Contact Output

Activates when Protective Function is Operating. AC250V, 1A or less;
DC30V, 1A or less.
Fault: 30A-30C Closed (30B-30C Open)
Normal: 30B-30C Closed (30A-30C Open)

Output signal

Contact

AXA, AXC

Multi-Function Output
Relay

Use After Defining Multi-Function Output Terminal. AC250V, 1A or less;
DC30V, 1A or less.

Comm.

CN3

Communication Port

Keypad Connection Port.

Tightening Torque: 5.2 lb-in maximum.

!