HP 30 HP30 User Manual

Page 196

Advertising
background image

Chapter 8 - Troubleshooting & Maintenance

8-2

Keypad Display

LCD

7-Segment

Protective

Function

Description

Option (**)

OPT

Option Fault

Fault at the internal option of the inverter.

HW-Diag HW

Inverter H/W

Fault

A fault signal is output when an error occurs to the control circuitry of the
inverter. There are the Wdog error, the EEP error, and the ADC Offset for this
fault

COM Error

CPU Error

Err

Communication

Error

This fault is displayed when the inverter cannot communicate with the keypad.

LOP
LOR
LOV

LOI

LOX

LP
LR
LV

LI

LX

Operating Method

when the

Frequency

Reference is Lost

According to the I/O-48 [Operating Method when the Frequency Reference is
Lost] setting, there are three modes: continue operation, decelerate and stop,
and free run,
LOP: Displayed when option frequency reference is lost (DPRAM time out)
LOR:

Displayed when option frequency reference is lost (Communication

network fault)
LOV: Displayed when ‘V1’ analog frequency reference is lost.
LOI: Displayed when ‘I‘ analog frequency reference is lost.
LOX: Displayed when sun-board (V2, ENC) analog frequency reference is lost.

Inv. OLT

IOLT

Inverter Overload

The inverter turns off its output when the output current of the inverter flows
more than the rated level (150% for 1 minute, 200% for 0.5 seconds).

NTC open

NTC

Thermal Sensor

Opened

Inverter uses NC thermal sensor for detecting heat sink temperature. If this
message is displayed, the thermal sensor wire may be cut. (Inverter keeps
operating)

MC Fail

MCF

Magnetic

contactor fault

This fault is displayed when input power is not applied or M/C inside the inverter
becomes faulty.


To reset fault perform one of the following:

} Press RESET key on the keypad.
} Close RST-CM terminals.

} Cycle power to the inverter.


If a problem persists, please contact the factory or your local distributor.

Advertising