HP 30 HP30 User Manual

Page 80

Advertising
background image

Chapter 5 - Parameter List

5-20

Keypad Display

Setting Range

Code

Description

LCD

7-Segment

LCD

7-Segment

Units

Factory

Default

Adj.

During

Run

Page

APP-02

27

Traverse Amplitude

Trv. Amp

02

0.0 to 20.0 [%]

0.1

0.0 [%]

Yes

6-2

APP-03

Traverse Scramble
Amplitude

Trv. Scr

03

0.0 to 50.0 [%]

0.1

0.0 [%]

Yes

6-2

APP-04 Traverse Accel Time

Trv Acc Time

04

0 to 6000 [sec]

0.1

2.0 [sec]

Yes

6-2

APP-05 Traverse Decel Time

Trv Dec Time

05

0 to 6000 [sec]

0.1

3.0 [sec]

Yes

6-2

APP-06

Traverse Offset (Hi)
Setting

Trv Off Hi

06

0.0 to 20.0 [%]

0.1

0.0 [%]

Yes

6-2

APP-07

Traverse Offset (Lo)
Setting

Trv Off Lo

07

0.0 to 20.0 [%]

0.1

0.0 [%]

Yes

6-2

APP-08

28

Running Auxiliary Motor
Number Display

Aux Mot Run

08

- -

-

-

6-2

APP-09

Starting Aux. Motor
Selection

Starting Aux

09

1 to 4

1

1

Yes

6-2

APP-10

Operation Time Display
on Auto Change

Auto Op Time

10

- -

-

-

6-2

APP-11

Start Frequency of Aux.
Motor 1

Start freq 1

11

0 to FU1-20

0.01 49.99 [Hz] Yes

APP-12

Start Frequency of Aux.
Motor 2

Start freq 2

12

0 to FU1-20

0.01 49.99 [Hz] Yes

APP-13

Start Frequency of Aux.
Motor 3

Start freq 3

13

0 to FU1-20

0.01 49.99 [Hz] Yes

APP-14

Start Frequency of Aux.
Motor 4

Start freq 4

14

0 to FU1-20

0.01 49.99 [Hz] Yes

6-2

APP-15

Stop Frequency of Aux.
Motor 1

Stop freq 1

15

0 to FU1-20

0.01 15.00 [Hz] Yes

APP-16

Stop Frequency of Aux.
Motor 2

Stop freq 2

16

0 to FU1-20

0.01 15.00 [Hz] Yes

APP-17

Stop Frequency of Aux.
Motor 3

Stop freq 3

17

0 to FU1-20

0.01 15.00 [Hz]] Yes

APP-18

Stop Frequency of Aux.
Motor 4

Stop freq 4

18

0 to FU1-20

0.01 15.00 [Hz] Yes

6-2

APP-19

Delay Time before
Operating Aux Motor

Aux start DT

19

0 to 9999 [sec]

0.1

60.0 [sec]

Yes

APP-20

Delay Time before
Stopping Aux Motor

Aux stop DT

20

0 to 9999 [sec]

0.1

60.0 [sec]

Yes

6-2

APP-21 The Number of Aux Motor

Nbr Aux’s

21

0 to 4

1

4

Yes

6-2

No 0

APP-22 PID Bypass Selection

Regul Bypass

22

Yes 1

- No Yes

6-2

APP-23 Sleep Delay Time

Sleep Delay

23

0 to 9999 [sec]

0.1

60.0 [sec]

Yes

6-2

APP-24 Sleep Frequency

Sleep Freq

24

0 to FU1-20

0.01 19.00 [Hz] Yes

6-2

27

Code APP-02 through APP-07 appears only when APP-01 is set to ‘Traverse’.

28

Code APP-08 through APP-31 appears only when APP-01 is set to ‘MMC’.

Advertising