Chapter 6 - Parameter Description [FU2]

6-17

Note: When the reference frequency is set inside the jump

frequency, the output frequency goes to the frequency
marked by “

n

” symbol.

Note: If one frequency jump range is required, set all ranges

to the same range.


FU2-17: Start Curve for S-Curve Accel/Decel
Pattern
FU2-18: End Curve for S-Curve Accel/Decel
Pattern











This parameter is used to adjust the Accel and Decel
pattern when ‘S-Curve’ is selected in FU1-05 and FU1-06
respectively. To use this function, the Reference
Frequency for Accel and Decel set in FU2-70 should be
set to ‘Delta freq’.












[S0Curve Adjustment]


Actual Accel Time = DRV-01 + (DRV-01 * FU2-17)/2 +
(DRV-01*FU2-18)/2

Actual Decel Time = DRV-02 + (DRV-02 * FU2-17)/2 +
(DRV-02*FU2-18)/2

Ex) If DRV-10: 1 sec, FU2-17: 40%, FU2-18: 20%,
Actual Accel Time = 1 sec + (1sec*0.4)/2 + (1sec*0.2)/2 =
1.3 sec

FU2-19: Input/Output Phase Loss Protection (Bit
Set)






This function is used to cut the inverter output off in case of
phase loss in either input power or inverter output.

FU2-19 [Phase Loss Protection Select]

Setting Range

2

nd

bit 1

st

bit

FU2-19

Description

0

0

00

Phase loss protection does not work

0

1

01

Protect inverter from output phase loss

1

0

10

Protect inverter from input phase loss

1 1 11

Protect inverter from input and output
phase loss




FU2-20: Power ON Start Selection






If FUN-20 is set to ‘No’, restart the inverter by cycling the
FX or RX terminal to CM terminal after power has been
restored.
If FUN-20 is set to ‘Yes’, the inverter will restart after power
is restored. If the motor is rotating by inertia at the time
power is restored, the inverter may trip. To avoid this trip,
use ‘Speed Search’ function by setting FU2-22 to ‘1xxx’.







FU2

► Trip select

19 00

00

19

Factory Default:

00

00

FU2

►Power-on run

20 --- No ---

0

20

Factory Default:

No

0

Related Functions: FU2-22 to FU2-25 [Speed Search]

FU2

► Start Curve

17 40 %

40

17

Factory Default:

40% 40

FU2

► End Curve

18 40 %

40

18

Factory Default:

40% 40

Output Frequency

Time

Max. Freq./2

FU2-17 FU2-18

FU2-17 FU2-18

Linear Linear

Advertising